Why work with us?

With over 20 years of bricklaying experience, the JRC team has built a strong reputation for cost effective and professional bricklaying solutions. We are fully licensed and insured, and our Melbourne bricklayers deliver specialist bricklaying and blocklaying services throughout the South Eastern Suburbs of Melbourne.

JRC have a demonstrated ability to run multiple projects and always supply enough labour to meet and exceed programme deadlines.

We're happy to travel

From Wantirna to Werribee we cover the Greater Melbourne area and continue to travel to do what we love. No job is too small or too big. We'll be there on time and with a professional approach to any job.

Services

We offer an extensive list of services to suit all requirements.

Bricklaying

At JRC our team of highly skilled and experienced tradesmen are capable with all aspects of Brickwork construction. We have the skills and processes in place to meet your exact requirements. We have a proven track record in the delivery of technically challenging projects. You will find our team easily accessible and willing to give advice through to the completion of your project.

Blocklaying

At JRC we have laid hundreds of thousands of square metres of perfect blockwork.

We have an experienced and fully trained workforce committed to providing quality workmanship whilst exceeding client expectations, delivered on time and on budget, within a safe environment.

JRC know what is expected of us and more importantly, our clients know what to expect from us, a consistent and professionally delivered service with a name built on honesty and quality.

We will service anywhere in Melbourne:

  • Sandringham
  • Caufield
  • Brighton
  • Elsternwick
  • Frankston
  • Cranbourne
  • Berwick
  • Pakenham
  • Dandenong
  • Belgrave
  • Bayswater
  • Wantirna

No single leaf in an exit door should be less than 28 in wide or more than 48 in wide. Minimum nominal width of opening should be at least: 36 in for single corridor or exit doors 32 in for each of a pair of corridor or exit doors with central mullion 48 in for a pair of doors with no central mullion 32 in for doors to all occupiable and habitable rooms 44 in for doors to rooms used by bedridden patients and single doors used by patients in such buildings as hospitals, sanitariums, and nursing homes 32 in for toilet-room doors Jambs, stops, and door thickness when the door is open should not restrict the required width of opening by more than 3 in for each 22 in of width. Nominal opening height for exit and corridor doors should be at least 6 ft 8 in. Jambs, stops, sills, and closures should not reduce the clear opening to less than 6 ft 6 in. For a specific type of occupancy, the number of exit doors required in each story of a multistory building and the minimum width permitted for each door can be determined from the maximum capacity listed in Art. 3.5.10. The maximum sizes of openings permitted in fire barriers are given in Table 11.19, p. 11.119. Safety at Entrances. Because of the heavy flow of traffic at building entrances, safety provisions at entrance doors are an important design consideration. Account must be taken of the location of such doors in the building faces, flow of outdoor traffic, and type and volume of traffic generated by the building. Following are some design recommendations: Arc of a door swing should exceed 90. An entrance should always be set back from the building face. Hinge jambs of swinging doors should be located at least 6 in from a wall perpendicular to the building face. If hinge jambs for two doors have to be placed close together, there should be enough distance between them to permit the doors to swing through an arc of 110. If several doors swinging in the same direction are placed close together in the same plane, they should be separated by center lights and should also have sidelights, to enable the doors to swing through 110 arcs. If doors hung on center pivots are arranged in pairs, they should be hinged at the side jambs and not at the central mullion. The floor on both sides of an exit door should be substantially level for a distance on each side equal to at least the width of the widest single leaf of the door. If, however, the exit discharges to the outside, the level outside the door may be one step lower than inside, but not more than 71/2% in lower. A wall or partition above a door or window opening must be adequately supported by a structural member. In design of such a member, stiffness as well as strength must be taken into account. Excessive deflection could interfere with door operation. It is common practice to install a frame along the perimeter of a door opening, to support the door. Anchored to the wall, the frame usually also serves as trim around the opening. In design of door framing, wind loads are generally more critical than dead loads imposed by the wall or partition above. Wind load should be taken as at least 15 lb / ft2. Under this loading, maximum deflection of framing members should not exceed 3/4 in or 1/175 the clear span. The design should take into account the fact that wind forces acting outward may be larger than those acting inward. Door framing should generally be made independent of other framing. Ordinary doors may be classified as exterior or interior doors. Exterior doors are those that are installed in an opening in a wall that separates an interior space from outdoors. Serving as an entrance or an exit door, or both, these doors must be capable of excluding weather but usually need not be fire rated. Interior doors are those installed in an opening in a wall or partition between two interior spaces. Such doors are not required to exclude weather but may be required to bar passage

The characteristic unconfined compressive strength (fuc) values now supplied for a traditional sized brick are approximately 60% of the previously used characteristic confined compressive strength values. It is important to note that this difference is due to the altered approach used when determining the values and not a reduction in strength. Refer to section 3 of Think Brick Australia Manual 2: The Properties of Clay Masonry Units for further information on compressive strength measurements. Brick Properties Brick Technical Manual 7 1.4 Durability Salt Attack The durability of a brick is a measure of its resistance to attack by soluble salts. The test method used to determine the durability of bricks is given in AS/ NZS 4456.10. The suitability of the units for use in a given environment determines their salt attack resistance category. The National Consruction Code (NCC) defines the environment with three exposure classifications for brick: 1. Exposure Grade (EXP) Suitable for use in external walls exposed to aggressive environments, such as:

Fan-Coil Terminal Units. A fan-coil terminal device consists of a fan or blower section, chilled-water coil, hot-water heating coil or electric-resistance heating elements, filter, return-air connection, and a housing for these components with an opening for ventilation air. The electric-resistance heating coil is often used with two-pipe systems to provide the performance of a four-pipe system without the cost of the two extra pipes for hot water, insulation, pumps, etc. Fan-coil units may be floor mounted, ceiling mounted-exposed or ceiling mounted-recessed, or ceiling mounted-recessed with supply- and return-air ductwork. When furnished with heating coils, the units are usually mounted on the outside wall or under a window, to neutralize the effects of perimeter heat losses. Built-in centrifugal fans recirculate room air through the cooling coil. Chilled water circulating through the coil absorbs the room heat load. Ventilation air that is conditioned by another remote central plant is ducted throughout the building and supplied directly to the room or room terminal devices, such as a fan-coil unit. A room thermostat varies the amount of cooling water passing through the cooling coil, thus varying the discharge temperature from the terminal unit and satisfying the room thermostat. Induction Terminal Units. These units are frequently used in large office buildings. The units are served by a remote air-handling unit that provides high-pressure conditioned air, which may be heated or cooled and is referred to as primary air. It is distributed to individual induction units that are located on the outside walls of each room or zone. At the terminal induction unit, a flow of high-pressure primarily air through several nozzles induces a flow of room air through the heating or cooling coil in the unit. Room air mixes with the primary air to provide a mixedair temperature that satisfies the thermal requirements of the space. In most systems, the ratio of induced air to primary air is about 4 to 1. FIGURE 13.40 Control circuit for an air-conditioning system in which the thermostat controls compressor operation. The induction system is a large energy consumer because of the extra power required to maintain the high pressure necessary to deliver the primary air to the room induction nozzles and induce room air to flow through the unit coils. Also, the induction terminal unit operates simultaneously with heating and cooling, wasting energy as in a terminal-reheat type of operation. Air-water systems generally have substantially lower installed and operating costs than all-air systems. They do not, however, provide as good control over room temperature, humidity, air quality, air movement, and noise. The best control of an air-water system is achieved with a fan-coil unit with supplemental ventilation air from a central, primary-air system that provides ventilation air. (H. E. Bovay, Jr., Handbook of Mechanical and Electrical Systems for Buildings, and N. R. Grimm and R. C. Rosaler, Handbook of HVAC Design, McGraw-Hill Publishing Company, New York.) One commonly used system has a thermostat wired in series with the compressor holding-coil circuit (Fig. 13.40). Thus the compressor will stop and start as called for by room conditions. The high-low pressure switch in series with the thermostat is a safety device that stops the compressor when the head pressure is too high and when the suction pressure approaches the freezing temperature of the coil. A liquid solenoid will shut off the flow of refrigerant when the compressor stops, to prevent flooding the coil back to the compressor during the off cycle. This valve may be eliminated when the air-handling unit and compressor are close together. A second type of control is the pump-down system (Fig. 13.41). The thermostat shuts off the flow of the refrigerant, but the compressor will keep running. With the refrigerant supply cut off, the back pressure drops after all the liquid in the coil vaporizes. Then, the high-low pressure switch cuts off the compressor. Either of these two systems is satisfactory. However, the remainder of this discussion will be restricted to the pump-down system. Additional safety controls are provided on packaged units to reduce compressor burnouts and increase the average life of these units. The controls include crankcase FIGURE 13.41 Pump-down system for control of air conditioning. heaters, motor-winding thermostats, and nonrecycling timers. These controls are usually prewired in the factory. The manufacturer supplies installation and wiring instructions for interconnecting the various components of the air-conditioning


Website built by Justin O’Dea www.webdeveloperdocklands.com.au

xvideosxvideosxvideosxvideosxvideosxvideosxvideosxvideosxvideosxvideosxvideosxvideos